Our Products

JJCD10 Piercing Grounding Protection

Short Description:

• Tested for watertightness at a voltage of 6 kV for 30 min in a water bath

• Potential free tightening bolts allow safe installations on life lines

• Bimetallic, suitable for aluminium and copper conductors

• Long neck 13 mm shear head nut ensuring reliable installations

• Components not isolated, end cap attached to body

• Insulation material made of weather and UV resistant glass fibre reinforced polymer


Product Detail

DRAWING

Product Tags

BASIS  DATA

Type Voltage  Conductor  Dimension (mm)   Bolt number Puncture depth
Nominal current
(KV) (mm2) A B H (A) PCS (mm)
JJCD10-25/95 10 25-95 144.5 140 92.5 257 2 4-5
JJCD10-16/120 11 16-120 148 120 86 316 2 4-5
JJCD10-35/120 10 35-120 148 120 86 316 2 4-5
JJCD10-95/185 10 95-185 152 140 112.5 476 2 4-5
JJCD10-150/240 10 150-240 160 140 112.5 476 2 4-5